TST320 is a module with MODBUS RTU interface and 2 inputs for thermocouples. Crafted for a range of industrial applications, it provides precise temperature readings across a variety of thermocouple types, making it an ideal solution for temperature measurements in industrial processes. The module’s unparalleled compatibility supports all thermocouples – J, K, T, N, E, B, R, and S – ensuring seamless integration into any setup. Its 24-bit ADC with DSP processing and ±0.1% accuracy provide exceptional measurement precision. Combined with ±0.19% CJC accuracy, your readings remain reliably precise. With an RS-485 interface supporting up to 63 nodes, communication with existing systems is effortless using Modbus RTU protocol. Designed for easy installation, it includes an integrated 120-ohm termination resistor for optimized signal integrity, simplifying setup. Safety is a top priority with a remarkable working isolation voltage of 1500Vrms, ensuring secure operation in industrial environments. TST320 2-channel thermocouple module enables engineers, technicians, and decision-makers to obtain real-time temperature data, enhancing process efficiency, product quality, and system reliability.
Features:
• 24-bit ADC with DSP processing
• RS-485 interface supporting up to 63 nodes
• LED indicator displaying communication status
• Compatibility with all types of thermocouples
• Integrated 120-ohm termination resistor
• Firmware update capability via the interface
Εγγυήσεις - Επιστροφές: | |
Επιστροφή Χρημάτων: | Επισκευή - Αντικατάσταση: |
20 ημέρες | 36 μήνες |
Specifications | |
Physical characteristics | |
Dimensions | 35 x 86 x 59 mm (2 module enclosure) |
Weight | 75g |
Mounting | On 35 mm DIN top-hat rail |
Environmental limits | |
Operating temperature range | -20 to 60°C |
Operating relative humidity range | 10 to 90% (non-condensing) |
Storage temperature range | -25 to 65°C |
Storage relative humidity range | 5 to 95% (non-condensing) |
Ingress protection | IP40 (connections IP20) |
Power supply | |
Operating voltage range (including -15/+20% according to IEC 62368-1) | 5 to 30VDC |
Current consumption | 15mA@12V |
Thermocouples | |
Thermocouple types supported | J, K, T, N, E, B, R, and S |
Temperature resolution | 0.01° |
ADC conversation accuracy max) | ±0.1% |
CJC accuracy (max) | ±0.19% |
Input conversion rate for both channels | 1 sample per second With DSP (Digital Signal Processing) over 76865 samples for low-pass filtering and 50/60Hz notch filtering |
Thermocouple break detection | Available |
Interface | |
Protocol | Modbus RTU |
Physical layer | RS-485 serial line |
Number of bus transceivers | up to 63 |
Bus cable | Twisted, shielded, 2×0.5mm² |
Response time | ≤50ms Master response time-out ≥ Response time + Answer time The answer time depends on the number of bits and the baud rate. |
Connectors | |
Type | 3.81mm pitch screwless pluggable for 28 to 16 (AWG) / 0.081 to 1.31 (mm²) wires |
Ιsolation | |
Maximum working isolation voltage | 1500Vrms |