Intelligent single-phase ON-LINE UPS with full digital control, zero switching time, clear sine output voltage, high efficiency with Power Factor 1. They do not require electrical installation and enable battery expansion for greater autonomy thanks to their enhanced charger. They feature Rack / Tower support and can protect professional and lightweight industrial applications.
Features:
• True double-conversion technology
• High flexibility with Rack or Tower mounting
• Output power factor 1
• Output voltage regulation < 1%
• Higher output crest ratio 3:1
• 50Hz/60Hz frequency converter mode
• Programmable power management outlets
• Emergency power off function (EPO)
• Hot swappable battery design
• ECO mode for energy saving
• Provides over voltage cutt-off protection and surge immunity by MOV for ongoing equipment protection
• High power factor charger up to 1000W capacity with very low ripple current when charging battery
• Low input THDi to reduce power system pollution
• Adjustable charging current via LCD panel
• Smart battery charger design to optimize battery performance
• Generator compatible
• Cold Start
• Auto Restart
Warranties - Returns: | |
Money Return: | Repair - Replacement*: |
20 days | 24 months |
*Batteries are accompanied by a 12-month warranty |
Specifications: | |
Phase | Single phase with ground |
Capacity | 1000 VA / 1000 W |
Input | |
Nominal Voltage | 200/208/220/230/240 VAC |
Voltage Range | 110-300 VAC ± 5% @ 50% load 160-300 VAC ± 5% @ 100% load |
Frequency Range | 40Hz ~ 70Hz |
Harmonic Distortion(THDi) | ≤ 5% @ nominal input voltage |
Power Factor | ≥ 0.99 @ nominal voltage (100% load) |
Output | |
Output Voltage | 200*/208*/220/230/240 VAC |
AC Voltage Regulation | ± 1% |
Frequency Range (Synchronized Range) |
57 ~ 63 Hz or 47 ~ 53 Hz |
Frequency Range (Batt. Mode) |
50 Hz ± 0.1Hz or 60Hz ± 0.1Hz |
Current Crest Ratio | 3:1 (max.) |
Harmonic Distortion | ≤ 2 % THD (Linear Load); ≤ 4 % THD (Non-linear load) |
Transfer Time | AC mode to Battery mode : Zero Inverter to Bypass : 4 ms (Typical) |
Waveform (Batt. Mode) | Pure Sinewave |
Overload AC mode | 110-130% : 5 min / 130-140%: 30 sec / >140% : 1.5 sec to 100ms |
Outlets | 8 x IEC 320 C13 |
Efficiency | |
AC Mode | ≥ 90% @ full charged battery |
ECO Mode | ≥ 96% @ full charged battery |
Battery Mode | ≥ 88% |
Battery | |
Battery Type (VRLA) | 12 V / 9 AH |
Numbers | 2 |
Typical Recharge Time | 3 hours recover to 95% capacity for internal battery@ 2A charging current |
Charging Current | Default 2A, max. 12A adjustable |
Charging Voltage | 27.4 VDC ± 1% |
Physical | |
Dimension, DxWxH (mm) | 410 x 438 x 88 |
Net Weight (without battery) |
6.6 kgs |
Net Weight (w/built-int battery) |
11.6 kgs |
Environment | |
Humidity | 5-95 % RH @ 0- 40°C (non-condensing) |
Noise Level | Less than 50dBA @ 1 Meter |
Altitude | 10% de-rating for over 1000m (The altitude should not exceed 3000m) |
Management | |
Smart RS-232/USB & Software | Supports Windows® 2000/2003/ XP/ Vista/ 2008/ 7/ 8, Linux and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
Standard | |
EMC/safety | EMC EN62040-2 C2 / EN 62040 - 1 / EN 62040 – 3 / RoHS 2 |
*De-rate capacity to 80% when the output voltage is adjusted to 200VAC/208VAC.